UPS management with NUT

UPS management with NUT

Any server must be always connected to an UPS unit

You really need to protect your server from electrical surges, power cuts or outages. A common way to achieve that protection is with a Uninterruptible Power Supply (UPS) unit, like the one part of this guide’s hardware setup.

This chapter explains how to make your Proxmox VE host monitor the UPS unit with a generic package called NUT (Network UPS Tool). However, be aware that your UPS unit’s brand may already have its own particular software for UPS management.

Important

NUT may not support your concrete UPS unit
Still, it may have compatible drivers for your UPS unit’s brand. Check in the NUT hardware compatibility list to verify if your brand or model line has compatible drivers there.

Connecting your UPS with your PVE node using NUT

This chapter uses the Eaton 3S700D UPS unit listed in the hardware setup. This model (and similar ones) comes with a USB 2.0 cable to connect the UPS unit with any computer.

Warning

This procedure is for UPS units connected through USB
If your UPS unit does not come with a USB cable, you cannot proceed with the instructions explained below.

Assuming your UPS unit has the required USB cable, proceed to configure it in your Proxmox VE server:

  1. First, check the following:

    • Your server is plugged in one of your UPS’s battery-protected sockets.
    • You have your UPS connected with its USB cable to a USB plug in your server.
    • The UPS unit is on. If it were not, you would not be able to switch your server on.
  2. With your Proxmox VE server running, get into the pve node through a root shell and execute the lsusb command:

    $ lsusb
    Bus 001 Device 001: ID 1d6b:0002 Linux Foundation 2.0 root hub
    Bus 001 Device 003: ID 05e3:0608 Genesys Logic, Inc. Hub
    Bus 001 Device 004: ID 0bda:0129 Realtek Semiconductor Corp. RTS5129 Card Reader Controller
    Bus 001 Device 005: ID 046d:c52b Logitech, Inc. Unifying Receiver
    Bus 001 Device 006: ID 0463:ffff MGE UPS Systems UPS
    Bus 002 Device 001: ID 1d6b:0003 Linux Foundation 3.0 root hub
    Bus 002 Device 002: ID 152d:0578 JMicron Technology Corp. / JMicron USA Technology Corp. JMS578 SATA 6Gb/s

    The lsusb returns a list of the USB devices currently connected to your physical server. Please notice how the Eaton 3S700D UPS unit is listed in the Bus 001 Device 006 line with the rather misleading name MGE UPS Systems UPS, confirming the correct connection of the unit to the pve node.

  3. Install the NUT software package:

    $ apt install -y nut
  4. You need to configure NUT properly to make it manage your UPS unit. There are several files to change, start by editing /etc/nut/nut.conf. But before you change it, first make a backup of it:

    $ cd /etc/nut
    $ cp nut.conf nut.conf.orig

    Now you can edit the nut.conf file. In it, there is only one line you have to modify:

    MODE=none

    This MODE line must be changed into the following:

    MODE=standalone

    By setting the standalone mode you’re enabling NUT to work in local mode or, in other words, it will “worry” only about your pve node.

    Note

    The nut.conf file has comments explaining configuration details
    Check the comments in the nut.conf to have a better idea of which are the modes that NUT supports.

  5. You need to tell NUT about the UPS unit connected to your system. To do that, you must edit the file /etc/nut/ups.conf, so make a backup of it:

    $ cp ups.conf ups.conf.orig

    Then, append the following parameters to the ups.conf file, although with values fitting for your UPS unit:

    [eaton]
      driver = usbhid-ups
      port = auto
      desc = "Eaton 3S700D"

    The parameters above mean this:

    • [eaton]
      This is the name that will identify your UPS unit in NUT. This can be any string of characters, but without spaces. Type something there that truly identifies your UPS in a clear manner.

    • driver
      Here you indicate NUT how to connect to your UPS unit. For UPS units with their data port plugged in a USB, the correct value is usbhid-ups.

    • port
      For an USB connection this has to be left to auto.

    • desc
      This is just a descriptive string where you can type the full name and model of your UPS unit, or anything else you might prefer.

  6. At this point, you can check if NUT can start its driver and detect your UPS unit properly:

    $ upsdrvctl start
    Network UPS Tools - UPS driver controller 2.8.1
    Network UPS Tools - Generic HID driver 0.52 (2.8.1)
    USB communication driver (libusb 1.0) 0.46
    Using subdriver: MGE HID 1.46

    The command tells you what components it is using and, in the last line, also indicates you what driver NUT used to connect to your particular UPS. In this guide’s scenario, you can see it is using the correct MGE subdriver.

    On the other hand, if you get the following warnings:

    libusb1: Could not open any HID devices: insufficient permissions on everything
    No matching HID UPS found
    upsnotify: notify about state 4 with libsystemd: was requested, but not running as a service unit now, will not spam more about it
    upsnotify: failed to notify about state 4: no notification tech defined, will not spam more about it
    Driver failed to start (exit status=1)

    Just reboot your Proxmox VE server and try the upsdrvctl start command again, it should run fine this time.

    Note

    Do not worry if you get a “Duplicate driver” warning
    In the output of the upsdrvctl start command you may get a warning like this one:

    Duplicate driver instance detected (PID file /run/nut/usbhid-ups-eaton.pid exists)! Terminating other driver!

    It seems that NUT already creates automatically a driver for the UPS unit in the moment it is configured in the ups.conf file. This is not an issue at this point, and NUT itself takes care of this duplicity.

  7. Configure the NUT daemon by editing the file /etc/nut/upsd.conf. Again, make a backup first:

    $ cp upsd.conf upsd.conf.orig

    Edit the upsd.conf file to uncomment only the LISTEN line referred to the IPv4 connection. It should end looking as follows:

    # LISTEN <IP address or name> [<port>]
    LISTEN 127.0.0.1 3493
    # LISTEN ::1 3493

    The LISTEN lines declares on which ports the upsd daemon will listen, and provides a basic access control mechanism. Uncomment the IPv6 line when you use this protocol in your network setup.

  8. In NUT there are also users, which are NOT the same ones as in the passwd file of your pve node. At this point, you require two user:

    • One for the NUT monitor agent (upsmon).
    • Other for acting as a NUT ups administrator(upsadmin).

    To add them, you must edit the file /etc/nut/upsd.users. First, back it up:

    $ cp upsd.users upsd.users.orig

    Then, append to upsd.users the following configuration block:

    [upsmon]
        password = s3c4R3_p4sSw0rD!
        upsmon primary
    
    [upsadm]
        password = D1Ff3rEnT_s3c4R3_p4sSw0rD!
        actions = SET
        instcmds = ALL

    The parameters shown above mean the following:

    • [upsmon]/[upsadm]
      This is the NUT user’s name. It can be any string, but with no spaces.

    • password
      The NUT user’s password. Bear in mind that this is an unencrypted configuration file. Be careful with who can access it.

    • upsmon primary
      Roughly speaking, this line means that the NUT user is from a machine directly connected to the UPS unit, and that NUT should be run with high privileges there.

      Note

      Learn more about UPS primary and secondary types in the NUT official documentation
      The UPS primary and secondary types are further explained in the NUT upsmon man documentation, in the UPS types section.

    • actions = SET
      Allows the NUT user to set values on the managed UPS unit.

    • instcmds = ALL
      Allows the NUT user to execute all available instant commands supported by the managed UPS unit.

  9. Finally, configure the NUT monitoring service that watches over the UPS unit. The configuration file you have to edit is /etc/nut/upsmon.conf, so back it up:

    $ cp upsmon.conf upsmon.conf.orig

    Then, do the following in the upsmon.conf file:

    • Search for and comment out the lines of the RBWARNTIME and SHUTDOWNCMD parameters:

      # --------------------------------------------------------------------------
      # RBWARNTIME - replace battery warning time in seconds
      #
      # upsmon will normally warn you about a battery that needs to be replaced
      # every 43200 seconds, which is 12 hours.  It does this by triggering a
      # NOTIFY_REPLBATT which is then handled by the usual notify structure
      # you've defined above.
      #
      # If this number is not to your liking, override it here.
      
      #RBWARNTIME 43200
      # --------------------------------------------------------------------------
      # SHUTDOWNCMD "<command>"
      #
      # upsmon runs this command when the system needs to be brought down.
      #
      # This should work just about everywhere ... if it doesn't, well, change it,
      # perhaps to a more complicated custom script.
      #
      # Note that while you experiment with the initial setup and want to test how
      # your configuration reacts to power state changes and ultimately when power
      # is reported to go critical, but do not want your system to actually turn
      # off, consider setting the SHUTDOWNCMD temporarily to do something benign -
      # such as posting a message with 'logger' or 'wall' or 'mailx'. Do be careful
      # to plug the UPS back into the wall in a timely fashion.
      #
      # For Windows setup use something like:
      # SHUTDOWNCMD "C:\\WINDOWS\\system32\\shutdown.exe -s -t 0"
      # If you have command line using space character you have to add double quote to them, like this:
      # SHUTDOWNCMD "\"C:\\Program Files\\some command.bat\" -first_arg -second_arg"
      # Or use the old DOS 8.3 file name, like this:
      # SHUTDOWNCMD "C:\\PROGRA~1\\SOMECO~1.bat -first_arg -second_arg"
      
      #SHUTDOWNCMD "/sbin/shutdown -h +0"
    • Append the following lines at the end of the upsmon.conf file:

      # --------------------------------------------------------------------------
      # Customized settings
      
      MONITOR eaton@localhost 1 upsmon s3c4R3_p4sSw0rD! primary
      SHUTDOWNCMD "logger -t upsmon.conf \"SHUTDOWNCMD calling /sbin/shutdown to shut down system\" ; /sbin/shutdown -h +0"
      
      NOTIFYMSG ONLINE "UPS %s: On line power."
      NOTIFYMSG ONBATT "UPS %s: On battery."
      NOTIFYMSG LOWBATT "UPS %s: Battery is low."
      NOTIFYMSG REPLBATT "UPS %s: Battery needs to be replaced."
      NOTIFYMSG FSD "UPS %s: Forced shutdown in progress."
      NOTIFYMSG SHUTDOWN "Auto logout and shutdown proceeding."
      NOTIFYMSG COMMOK "UPS %s: Communications (re-)established."
      NOTIFYMSG COMMBAD "UPS %s: Communications lost."
      NOTIFYMSG NOCOMM "UPS %s: Not available."
      NOTIFYMSG NOPARENT "upsmon parent dead, shutdown impossible."
      
      NOTIFYFLAG ONLINE SYSLOG
      NOTIFYFLAG ONBATT SYSLOG
      NOTIFYFLAG LOWBATT SYSLOG
      NOTIFYFLAG REPLBATT SYSLOG
      NOTIFYFLAG FSD SYSLOG
      NOTIFYFLAG SHUTDOWN SYSLOG
      NOTIFYFLAG COMMOK SYSLOG
      NOTIFYFLAG COMMBAD SYSLOG
      NOTIFYFLAG NOCOMM SYSLOG
      NOTIFYFLAG NOPARENT SYSLOG
      
      RBWARNTIME 7200 # 2 hours

    Here is an explanation for all the added parameters in the configuration snippet:

    • MONITOR
      This is the line where you must specify your UPS unit (eaton@localhost), the username (upsmon) and your NUT user’s password (s3c4R3_p4sSw0rD!). The number 1 indicates the number of power supplies feeding your system through the connected UPS.

    • SHUTDOWNCMD
      Declares the command to be used to shut down the host. In the line shown in the snippet, the command is prepared to write a log before it executes the system’s shut down.

    • NOTIFYMSG
      Each of these lines are assigning a text message to each NOTIFY event. Within each message, the marker %s is replaced by the name of the UPS unit producing the event. upsmon passes this message to the program wall to notify the event to the system administrator.

    • NOTIFYFLAG
      Each line declare what is to be done at each NOTIFY event. Up to three flags can be specified for each event. In the example, all events will be registered in the host’s /var/log/syslog log file.

    • RBWARNTIME
      When an UPS unit says it needs to have its battery replaced, upsmon will generate a NOTIFY_REPLBATT event. This parameter means that this warning will be repeated every this many seconds.

  10. Before you can try the configuration, restart the NUT-related services to be sure that they load with the right parameters:

    $ systemctl restart nut-client.service nut-server.service

    The service’s restart will take a couple of seconds, and should not return any line if everything goes fine.

  11. Check if the NUT services are working properly with your UPS unit:

    • upscmd -l upsunitname
      Lists the instant commands supported by the UPS unit named upsunitname (replace the placeholder string with the name you gave to your UPS back in point 5). Below you can see its output with this guide’s UPS unit:

      $ upscmd -l eaton
      Instant commands supported on UPS [eaton]:
      
      beeper.disable - Disable the UPS beeper
      beeper.enable - Enable the UPS beeper
      beeper.mute - Temporarily mute the UPS beeper
      beeper.off - Obsolete (use beeper.disable or beeper.mute)
      beeper.on - Obsolete (use beeper.enable)
      driver.killpower - Tell the driver daemon to initiate UPS shutdown; should be unlocked with driver.flag.allow_killpower option or variable setting
      driver.reload - Reload running driver configuration from the file system (only works for changes in some options)
      driver.reload-or-error - Reload running driver configuration from the file system (only works for changes in some options); return an error if something changed and could not be applied live (so the caller can restart it with new options)
      driver.reload-or-exit - Reload running driver configuration from the file system (only works for changes in some options); exit the running driver if something changed and could not be applied live (so service management framework can restart it with new options)
      load.off - Turn off the load immediately
      load.off.delay - Turn off the load with a delay (seconds)
      load.on - Turn on the load immediately
      load.on.delay - Turn on the load with a delay (seconds)
      shutdown.return - Turn off the load and return when power is back
      shutdown.stayoff - Turn off the load and remain off
      shutdown.stop - Stop a shutdown in progress
    • upsc upsunitname
      Returns the statistics from the UPS unit specified as upsunitname (again, replace this string with your own UPS unit’s name). See below the output this commands returns for this guide’s reference hardware:

      $ upsc eaton
      Init SSL without certificate database
      battery.charge: 100
      battery.charge.low: 20
      battery.runtime: 3840
      battery.type: PbAc
      device.mfr: EATON
      device.model: Eaton 3S 700
      device.serial: Blank
      device.type: ups
      driver.debug: 0
      driver.flag.allow_killpower: 0
      driver.name: usbhid-ups
      driver.parameter.pollfreq: 30
      driver.parameter.pollinterval: 2
      driver.parameter.port: auto
      driver.parameter.synchronous: auto
      driver.state: quiet
      driver.version: 2.8.1
      driver.version.data: MGE HID 1.46
      driver.version.internal: 0.52
      driver.version.usb: libusb-1.0.28 (API: 0x100010a)
      input.transfer.high: 264
      input.transfer.low: 184
      outlet.1.desc: PowerShare Outlet 1
      outlet.1.id: 1
      outlet.1.status: on
      outlet.1.switchable: no
      outlet.desc: Main Outlet
      outlet.id: 0
      outlet.switchable: yes
      output.frequency.nominal: 50
      output.voltage: 230.0
      output.voltage.nominal: 230
      ups.beeper.status: enabled
      ups.delay.shutdown: 20
      ups.delay.start: 30
      ups.firmware: 02.08.0010
      ups.load: 4
      ups.mfr: EATON
      ups.model: Eaton 3S 700
      ups.power.nominal: 700
      ups.productid: ffff
      ups.realpower: 22
      ups.serial: Blank
      ups.status: OL
      ups.timer.shutdown: -1
      ups.timer.start: -1
      ups.type: offline / line interactive
      ups.vendorid: 0463

Checking the NUT logs

NUT’s services write logs in the journal of the Proxmox VE system. Look out for them with the journalctl command:

  • nut-server log entries from the NUT server.
  • nut-monitor log entries from the NUT monitor.
  • upsd log entries from the UPS daemon.

Remember to check them out, specially when you have created or modified your NUT configuration. For instance, if NUT cannot connect with your UPS unit, you can see in your PVE system’s journal warning logs from the NUT monitor:

Aug 26 10:53:52 pve nut-monitor[6684]: UPS eaton@localhost: Not available.
Aug 26 10:53:57 pve nut-monitor[6684]: Poll UPS [eaton@localhost] failed -  Poll UPS [eaton@localhost] failed - [eaton] does not exist on server localhost

Executing instant commands on your UPS unit

To execute the so called instant commands on your UPS unit (wich you can list with upscmd -l upsunitname), you have to use the command upscmd with the NUT administrator user defined in the previous section. A safe way to test this is by disabling and enabling the beeper usually embedded in any UPS:

$ upscmd eaton beeper.disable
Username (root): upsadm
Password:
OK
$ upscmd eaton beeper.enable
Username (root): upsadm
Password:
OK

You can also execute the whole upscmd command in just one line:

$ upscmd -u upsadm -p D1Ff3rEnT_s3c4R3_p4sSw0rD! eaton beeper.disable

Warning

Use this one-line format only for task automation with shell scripts
Do not execute the upscmd with the password in your normal shell, to avoid exposing your password in your user’s shell history (the .bash_history text file in bash shells).

Also, remember that:

  1. You have to check out first with upscmd -l upsunitname which are the instant commands supported by your UPS unit.

  2. The NUT software cannot really know if the instant command has been executed on the UPS unit. It only sees what the UPS unit is answering back in response to the command’s request.

Other possibilities with NUT

If you feel curious about what else you can do with NUT, there is a pdf document providing a good number of configuration examples. Get it in this GitHub page.

Relevant system paths

Directories

  • /etc/nut
  • /var/log

Files

  • /etc/nut/nut.conf
  • /etc/nut/nut.conf.orig
  • /etc/nut/ups.conf
  • /etc/nut/ups.conf.orig
  • /etc/nut/upsd.conf
  • /etc/nut/upsd.conf.orig
  • /etc/nut/upsd.users
  • /etc/nut/upsd.users.orig
  • /etc/nut/upsmon.conf
  • /etc/nut/upsmon.conf.orig
  • /var/log/syslog

References

Network UPS Tools (NUT)

Related NUT contents

About UPS units